Carel Pressure Sensor SPK

Carel type P pressure sensors are cost-effective, highly accurate products that use piezoresistive technology, with a 0.5-4.5 ratiometric output and brass housing. Excellent EMC features make these sensors suitable for the harshest environments. These sensors can be directly installed on the refrigerant pipe (no capillary tube is needed) Compatible with the most common refrigerants. This series is excluded from the scope of the Pressure Equipment Directive 2014/68/EU (the sensor itself does not have safety function). The sensors are equipped with aesthetic o-rings to recognise the pressure range easily.

Electrical:

Power supply(protected aqainst polarity reversal) 5 Vdc +10%
Power supply overvoltage 18Vdc
Maximum reverse voltage 11Vdc
Current draw 5 mA typical
Output voltage 0.5-4.5 Vdc ratiometric
Short-circuit protection yes
Output load >47 kΩ
Response time 10 ms max
Insulation resistance 1 GΩ @ 50 Vdc
Electrical connector Male, 3-pin Metri-Pack 150
Electrical connector insulation material PBT 30GF
Electrical contact material and surface fnish material Cu Zn20, Ni 2-3μm Sn 5 + 2.5 μm
Cable See SPKC******accessory

Performance:

Operating temperature -40T135°C
Operating humidity 0-90%rH
Fluid temperature -40T135°C
Storage temperature -40T150°C
Ingress protection IP55, lP69K depending on the connector plugged in.For more details, see sensor table and SPKC****** accessory table.
Accuracy (including linearity, hysteresis, repeatability, calibration error)static error @25'C at 5.0Vdc ±1.2% FS
Temperature error ±0.013% FS/°C
Total error band (including linearity, hysteresis, repeatability, calibrationerror) relative to all operating temperature and humidity values ±1.5% FS at 5 Vdc (0T50°C) ±2.1% FS at 5 Vdc (-40T90°C) +2.6% FS at 5 Vdc (40T135°)"
Life cycle 10 million cycles, 0-100% FS

Series: